Mediando web vorlage

S90 combination penetration seal
"ZZ-Platte BDS-N" foam board Type approval No. Z-19.15-1861

 
Applications
Suited, in particular, as penetration seal for medium-sized to large wall and floor openings with low to medium cable/pipe assignment. Due to an extensive type approval, various proven installation options are available.

S90 combination penetration seal
ZZ-Steine 200 BDS-N foam blocks Type approval No. Z-19.15-1182

 
Applications
Temporary or permanent penetration seals for electrical cables of all types and diameters and for combustible and non-combustible pipes
Due to an extensive type approval, suited, in particular, for mixed installations of all types. Apart from that, no additional collars need to be provided when combustible pipes are passed through the penetration seal.
Tested for S90 fire resistance rating. For details, please refer to the type approval.

S90 cable penetration seal
ZZ-Steine 170 BDS-N foam blocks Type approval No. Z-19.15-1744

 
Applications
Temporary or permanent penetration seals for electrical cables of all types and diameters and for non-combustible pipes
Suited, in particular, for cables of any type and diameter, and for non-combustible pipes in wall and floor openings with frequently changing cable/pipe assignment.
Tested for S30, S60 and S90 fire resistance rating. For details of the S30 and S60 rating, please refer to the type approval.

S90 cable penetration seal
ZZ-Steine 120 BDS-N foam blocks Type approval No. Z-19.15-1743

 
Applications
Any type and diameter of temporary and permanent penetration seals for electrical cables and conduits.
Suited, in particular, for cables used for communication and data systems (telecommunication) up to diameters of 18 mm, which are passed through wall and floor openings with frequently changing cable assignment. For these applications, no "ZZ-Kabelwickel BDS-N" wrap is required.
Tested for S30, S60 and S90 fire resistance rating. For details of the S30 and S60 rating, please refer to the type approval.

S90 cable penetration seal
ZZ-Stopfen BDS foam plugs Type approval No. Z-19.15-1316

 
Applications
Any type and diameter of temporary and permanent penetration seals for electrical cables and conduits.
Suited, in particular, for all conventional core drilling diameters of up to 250 mm.
Tested for S30, S60 and S90 fire resistance rating. For details of the S30 and S60 rating, please refer to the type approval.

S90 cable penetration seal
ZZ-DoBo BDS foam plugs Type approval No. Z-19.15-1318

 
Applications
Any type and diameter of temporary and permanent penetration seals for electrical cables and conduits.
Suited, in particular, for microseals in lightweight partitions with standard diameters of 75 mm or 100 mm, which are produced with a hole saw. Additional frames made from non-combustible building boards are not required.
Tested for S30, S60 and S90 fire resistance rating. For details of the S30 and S60 rating, please refer to the type approval.

S90 cable penetration seal
ZZ-Box BDS foam box Type approval No. Z-19.15-1315

 
Applications
Any type and diameter of temporary and permanent penetration seals for electrical cables and conduits.
Suited, in particular, for penetration seals in lightweight partitions. Additional frames made from non-combustible building board material are not required.
Tested for S30, S60 and S90 fire resistance rating. For details of the S30 and S60 rating, please refer to the type approval.

S90 cable penetration seal
ZZ-Brandschutzmasse 1K single-component mastic Type approval No. Z-19.15-1642

 
Applications
permanent sealing of electric cables 18 mm
Suited, in particular, for microseals in fireproof walls and floors.
Tested for S90 fire resistance rating. For details, please refer to the type approval.

S90 cable penetration seal
"ZZ-Brandschutzschaum 2K" two-component foam Type approval No. Z-19.15-1649

 
Applications
Permanent fire barrier for any type and diameter of electrical cables and conduits
Suited, in particular, for difficult-to-access openings and openings accommodating a high level of installations.
Tested for S90 fire resistance rating. For details, please refer to the type approval.

R90 pipe penetration seal
ZZ-Brandschutzschaum 2K according to test certificate (abP) Test certificate (abP) No. P-3031/1264-MPA BS

 
Applications
Permanent fire barrier for non-combustible pipes
Suited, in particular, as penetration seal for individual pipes.

R90 Pipe penetration seal
"ZZ" collar Type approval No. Z-19.17-1659

 
Applications
Permanent fire barrier for combustible pipes
Suited, in particular, for installation in series, because no minimum clearances need to be considered.
Tested for R90 fire resistance rating in walls and floors, and R120 in floors. For details of R120 rating, please refer to the type approval.