Suited, in particular, for microseals in fireproof walls and floors.
Tested for S90 fire resistance rating. For details, please refer to the type approval.
Application in connection with structural members of fire-resistance class F90
Walls made from masonry according to DIN 1053-1, concrete and/or reinforced concrete according to DIN 1045, or aerated-concrete building boards according to DIN 4166 - from 100 mm
Floors made from concrete and/or reinforced concrete according to DIN 1045, or aerated concrete according to DIN 4223 - from 150 mm
Lightweight stud partitions with steel sub-structure, inside mineral-wool insulation (construction material class DIN 4102-A; melting point higher than 1000 °C), boarded with non-combustible building boards according to DIN 18180 on both sides - from 100 mm
maximum measurements of sealing system [mm]
fireproof wall
Ø 80
fireproof floor
Ø 80
lightweight partition
Ø 80
Minimum installation depth (penetration thickness)
100 mm
Scope of type approval
Any type of electrical cables up to a diameter of 18 mm (including optical fibres), except for waveguide cables
The sum total of the cross section of all cables may be up to 60% of the rough member opening.