S90 combination penetration seal
"ZZ-Platte BDS-N" foam board Type approval No. Z-19.15-1861

Applications
Suited, in particular, as penetration seal for medium-sized to large wall and floor openings with low to medium cable/pipe assignment. Due to an extensive type approval, various proven installation options are available.
Application in connection with structural members of fire-resistance class F90
Walls made from masonry according to DIN 1053-1, concrete and/or reinforced concrete according to DIN 1045, or aerated-concrete building boards according to DIN 4166 - from 100 mm
Floors made from concrete and/or reinforced concrete according to DIN 1045, or aerated concrete according to DIN 4223 - from 150 mm
Lightweight stud partitions with steel sub-structure, inside mineral-wool insulation (construction material class DIN 4102-A; melting point higher than 1000 °C), boarded with non-combustible building boards according to DIN 18180 on both sides - from 100 mm
maximum measurements of sealing system [mm]
fireproof wall (W x H) 1000 x 1000 (wall thickness from 175 mm) resp. 575 x 1000 or 800 x 400 (wall thickness from 100 mm)
fireproof floor (W x H) 600 x unlimited length
lightweight partition (W x H) 575 x 1000
Minimum installation depth (penetration thickness)
100 mm
Scope of type approval
Any type and diameter of electrical cables (including optical fibres), except for waveguide cables
Individual conduits made from plastic pipes for control purposes, up to outside pipe diameters of 15 mm
Cable support structures (cable channels, cable trays, cable ladders) made from steel, aluminium or plastic profiles.
Combustible pipes with outside pipe diameters of up to 110 mm and pipe wall thicknesses between 1.8 mm and 10.0 mm (for pipe diagrams, see type approval Z-19.15-1861).
Combustible and non-combustible pipes for piping installations handling non-flammable liquids and non-flammable gases (except for ventilation pipes), for pneumatic tube systems (transmission tubes) or for dust extraction pipes.
Non-combustible pipes made from steel, stainless steel and cast steel with outside pipe diameters of up to 168.3 mm and pipe wall thicknesses between 1.0 mm and 14.2 mm; and pipes made from copper with outside pipe diameters of up to 88.9 mm and and pipe wall thicknesses between 1.0 mm and 14.2 mm (for pipe diagrams, see type approval Z-19.15-1861).
Non-combustible pipes intended for piping systems for flammable liquids and flammable gases.
Section insulation made from mineral-fibre mats or tubes can either be passed through the penetration seal or end flush with the seal surface (for fields of application, insulation lengths and thicknesses, and pipe diagrams, see type approval Z-19.15-1861).
The sum total of the cross sections of all cables and pipes may come to a maximum of 60 % of the rough member opening.