R90 pipe penetration seal
ZZ-Brandschutzschaum 2K according to test certificate (abP) Test certificate (abP) No. P-3031/1264-MPA BS

Applications
Permanent fire barrier for non-combustible pipes
Suited, in particular, as penetration seal for individual pipes.
Application in connection with structural members of fire-resistance class F90
Walls made from masonry according to DIN 1053-1, concrete and/or reinforced concrete according to DIN 1045, or aerated concrete according to DIN 4166 as - from 150 mm
Floors made from concrete and/or reinforced concrete according to DIN 1045, or aerated concrete according to DIN 4223 - from 150 mm
maximum measurements of sealing system [mm]
fireproof wall Ø 200 or 200 x 200
fireproof floor Ø 200 or 200 x 200
Minimum installation depth (penetration thickness)
150 mm
Scope of type approval
Non-combustible pipes for piping installations handling non-flammable liquids and non-flammable gases (except ventilation pipes), for pneumatic tube systems (transmission tubes) or for dust extraction pipes. The prevention of fire spread with the media handled has not been demonstrated with this type approval. Adequate measures must be taken to prevent fire spread.
Non-combustible pipes made from steel, stainless steel and cast steel, and pipes made from copper, with outside pipe diameters of up to 88.9 mm and pipe wall thicknesses between 1.0 mm and 14.2 mm (for fields of application, insulation lengths and thicknesses, and pipe diagrams, see test certificate (AbP) No. P-3031/1264-MPA BS).
Non-combustible pipes intended for piping systems for flammable liquids and flammable gases.